Start-Up Type Ep 501 C - EBRO ARMATUREN EP 501 Démarrage Rapide

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

To stop X.TUNE, press the left or right selection key
Procedure:
Key
Action
MENU
press for
approx. 3 s
/
Select X.TUNE
RUN
Hold down
as long as countdown
(5 ...) is running
Press any key
EXIT
press
Tab. 11: Automatic adjustment of X.TUNE
You have to exit the main menu by pressing the left selection
key
EXIT
before the modified data is saved in the memory
(EEPROM). During the save process the save symbol is
indicated
on the display.
30
STOP
Description
Change from process level
setting level
During the automatic adjustment
messages are displayed indi-
cating the progress of the
X.TUNE
"TUNE #1... X.TUNE ready".
Return to main menu (MAIN)
Change from setting level
process level
english

16.3 Start-up Type EP 501 C

.
To be able to operate the positioner as a process controller, perform
the following steps:
1. S etting up the position controller:
Description see „16.2.1 Specifying the standard settings"
2. S etting up the process controller:
Enter the P.CONTROL auxiliary function into the main menu
(MAIN) via the configuration menu (ADD.FUNCTION).
Key
Action
MENU
press for approx. 3 s
/
Select ADD.FUNCTION
ENTER
press
/
Select P.CONTROL
ENTER
press
EXIT
press
The P.CONTROL function is now activated and entered in the
main menu (MAIN).
Tab. 12: Enter the P.CONTROL auxiliary function into the main menu
(MAIN)
Type EP 501
Start-Up

Publicité

Table des Matières
loading

Table des Matières