Connection Of External Position Sensors For Type Ep 501 L; Pneumatic Connection - EBRO ARMATUREN EP 501 Démarrage Rapide

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Type EP 501
Pneumaticconnection
12.1 Connection of external position
sensors for type EP 501 L
Connect 4 – 20 mA path sensor to the terminals 1 - 4 of the
type EP 501 L (see chapter „14.5.1 Terminal assignments of the
process actual value input").
Internal supply of the path sensor by Type EP 501 L:
→ Connection according to input type "4 – 20 mA - internally
supplied".
Separate supply of the path sensor:
→ Connection according to input type "4 – 20 mA - externally
supplied".
Attach remote sensor on the actuator.
The correct procedure is described in the instructions for the
path sensor.
Connect compressed air to the Type EP 501 L.
Connect Type EP 501 L pneumatically to the actuator.
Switch on Type EP 501 L operating voltage.
To obtain the best possible control precision, adjust the path
sensor so that path to be measured corresponds to the signal
range 4 – 20 mA (only if the path sensor includes this function).
In the ADD.FUNCTION menu activate the POS.SENSOR
function. Then select POS.SENSOR in the main menu and set
ANALOG.
The procedure is described in the operating instructions for the
device in the chapter "Starting up and operation of the process
controller / auxiliary functions / POS.SENSOR".
Run the X.TUNE function.
13

PNEUMATIC CONNECTION

DANGER!
Risk of injury from high pressure in the equipment!
▶ Before loosening the pneumatic lines and valves, turn off the
pressure and vent the pneumatic lines.
WARNING!
Risk of injury from improper installation!
▶ Installation may be carried out by authorized technicians only
and with the appropriate tools!
Risk of injury from unintentional activation of the system and
an uncontrolled restart!
▶ Secure system from unintentional activation.
▶ Following installation, ensure a controlled restart.
Deaeration connection
Fig. 9:
Pneumatic installation / Location of the connections
english
Supply pressure connection
1.4 – 7 bar (connection: P)
Working connection 2
(connection: A2)
Working connection 1
(connection: A1)
19