Safety End Positions - EBRO ARMATUREN EP 501 Démarrage Rapide

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Procedure:
Apply supply pressure (1.4 – 7 bar) to the supply pressure con-
nection P.
For single-acting actuators (control function A and B):
Connect one working connection (A1 or A2, depending on
required safety end position) to the chamber of the single-acting
actuator.
Safety end positions see chapter„13.1.1".
Seal a working connection which is not required with a plug.
For double-acting actuators (control function I):
Connect working connections A1 and A2 to the respective
chambers of the double-acting actuator.
Safety end positions see chapter „13.1.2".
Important information for perfect control behaviour!
This ensures that the control behaviour is not extremely
negatively affected in the upper stroke range on account of
too little pressure difference.
• keep the applied supply pressure at least 0.5 – 1 bar
above the pressure which is required to move the pneu-
matic actuator to its end position.
If fluctuations are greater, the control parameters measured
with the X.TUNE function are not optimum.
• during operation keep the fluctuations of the supply
pressure as low as possible (max. ±10%).
20
english
Type EP 501
Pneumaticconnection

13.1 Safety end positions

The safety end position following failure of the auxiliary electrical
power depends on the pneumatic connection of the actuator to the
working connections A1 or A2.
13.1.1 Single-acting actuators
Safety end positions after failure of the
Actuator system
auxiliary power
Connection
according to
„Fig. 10"
up
down
Connection
according to
Control function A
„Fig. 11"
Connection
according to
„Fig. 10"
up
down
Connection
according to
Control function B
„Fig. 11"
Tab. 3:
Safety end positions - single-acting actuators
electrical
pneumatic
auxiliary power
down
down
up
up
up
down