Process Display
Terminal assignment
Terminal
Terminal assignment
11
+ 0/4 to 20 mA signal
12
Signal ground (current, voltage, temperature)
13
+ 1 V, + thermocouples, - resistance thermometer signal (3/4 wire)
15
+ resistance thermometer signal (4-wire)
17
+ 30 V
19
+ resistance thermometer power supply (3-wire/4-wire)
4.2
Connecting the device
WARNING
!
Danger! Electric voltage!
‣
The entire connection of the device must take place while the device is de-energized.
4.2.1 Connecting the power supply
• Before wiring the device, ensure that the supply voltage corresponds to the specification on
the nameplate.
• For the 90 to 250 V AC version (power supply connection), a switch marked as a separator,
as well as an overvoltage organ (rated current ≤ 10 A), must be fitted in the supply line near
the device (easy to reach).
Fig. 5: Connecting the power supply
4.2.2 Connecting external sensors
Active and passive sensors with analog, TC, resistance and RTD sensors can be attached
to the device.
Wiring
G09-RIA452xx-04-10-xx-xx-000