GOK GWS 904 Instructions De Montage Et De D'utilisation page 40

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Pipe fitting – fitting for pipe assembly type 904 / 907
If the filling hole is located directly adjacent to the installation location of the limit indicator,
limit indicators with pipe fitting must be used.
Wall fitting – fitting for wall assembly type 905
Filling hole plug for limit indicator
Instead of the wall fitting, it is also possible to use a filling hole plug for limit
indicator type 906.
18 / 24
Limit indicator GWG - type GWS -issue 2
Suitable cable with sufficient cross-section and chemical
resistance against the operating media.
1. Open the cap
2. Connect the connection line to terminal
3. Tighten the screwed cable gland
4. Tightly close the cap
5. Skin 10mm of the end of the cable.
6. Provide for electrical connection:
• black or brown lead "+".
• blue lead "-".
• The wall fitting is supplied separately and must be connected
to the limit indicator.
• The wall fitting must be attached sufficiently.
• The free end of the limit indicator's cable is routed
perpendicularly to the ceiling or a nearby wall.
• If the filling hole plug is farther away from the tank (e.g.
regarding a central filling hole), limit indicators with cable
connection fitting
used. The connection between the cable connection fitting and
the wall fitting must be provided with a cable/line 2 x 1mm².
• The maximum length may be: 150m for 2 x 1mm²,
with sealing ring
.
with sealing ring
(order no. 15 379 00) and wall fitting are
250m for 2 x 1.5mm².
on the limit indicator.
.
.
Part No. 15 382 65