In particular, the settable events, are the following:
Disabled contact
Circuit breaker open
Circuit breaker closed
Overload pre-alarm 90% Ir
Overload alarm 105% Ir
Temperature alarm
for protection unit 75 °C
Generic trip
Overload trip (Ir)
* Equivalent to generic trip.
Protection unit MP6 - DMX
Short-circuit trip for short
time protection (Isd)
Short-circuit trip for
instantaneous protection (Ii)
Short-circuit trip for fixed instan-
taneous protection (Icw)
Ground fault trip (Ig)
Overtemperature trip
for protection unit 95 °C
Test button diagnostic trip
Generic electric fault *
3
81