terminal A -, to shield the photocells from external noise.
Be careful not to short circuit the system when the supply
phases are inverted!
PHOTOCELLS "AUTO-TEST" MONITORING (A+/A- TEST)
Connect the photocell transmitter to A+ TEST/A- and set DIP 7
to ON.
The monitoring consists of a functional test of the photocell run before every movement.
The gate movement is therefore permitted only if the photocells have passed the functional
test.
Caution: Photocell input monitoring can be enabled with DIP 7 to ON, or disabled with DIP 7
to OFF.
WARNING: If the AUTOTEST feature is enabled and only one photocell is connected, a jumper
must be made between the PHOT 1 and PHOT 2 terminals. If the jumper is not made,
the AUTOTEST fails and the gate will not move.
FAILED AUTO-TEST ALARM (DIP 7 ON)
If the photocell fails the monitoring test, an alarm is displayed by the blinker lighting up
and gate movement is not allowed. Normal operation can be restored only by repairing the
photocell and pressing one of the controls.
EDGES (SAFETY STRIPS) (COM A+/EDGE 1/EDGE 2) - Safety function PL "c" according to BS EN
13849-1
If engaged when closing, EDGE 1 reverses the motion in opening. If edge remains engaged, it
doesn't permit the closing.
If engaged during opening, EDGE 2 reverses the motion in closing. If edge remains engaged, it
doesn't permit the opening.
If edges are not used, jump the terminals COM A+/EDGE1/EDGE2.
The movement will restart at a slow speed until the opening or closing limit switch is reached.
EDGE ALARM
Flasher and buzzer are activated with 2 tones every 5 s for one minute.
STOP BUTTON (COM A+/STOP) - Safety function PL "c" according to BS EN13849-1
During the movement, the stop button will stop the gate.
If the STOP button is pressed when the gate is fully open (or partially using the pedestrian
command) the automatic closure will be temporarily excluded (if enabled via trimmer ACT with
led DL11 ON). It is therefore necessary to give a new command to close the gate.
Closing the gate will re-enable automatic closing (if enabled via trimmer ACT with led DL11 ON).
HEATER FUNCTION (DIP 13 - ON)
Allows the operator to always operate at a temperature suitable for the operation.
This device automatically turns on only when the gate is at a standstill and the opening or
closing limit-switch engaged, at an ambient temperature of the motor of 0° C, detected by the
sensor mounted on the board.
When the motor is in motion, the heater is turned OFF.
After 10 s that the gate remains stationary, the heater is activated (if the motor ambient
temperature is less than or equal to 0° C).
When the motor reaches a temperature of 3° C, the heater shuts down, maintaining the
environmental conditions at a constant temperature.
VISUAL AND SOUND ALARMS
FLASHER
IMPORTANT: This electronic panel can power only one flasher with flashing circuit (ACG7072)
24 V and 20 W maximum.
If you exceed 20 W, the electronic panel's logic will be compromised, with the system possibly
stopping.
PRE-FLASHING FUNCTION
DIP 5 OFF => the motor and flasher start simultaneously.
DIP 5 ON => the flasher starts 3 s before the motor.
BUZZER
Signals that the safety devices have triggered an alarm, alarm status and codes saved/deleted
in memory.
GATE OPEN 24 Vdc INDICATOR LIGHT (COM A+/SIGNAL -)
The light signals that the gate is open, partly open or not completely closed. Only when the gate
is completely closed does the light turn OFF.
During opening, it flashes slowly.
24 Vdc
When the gate is stationary or opened, it is permanently on.
Cont.
During closing, it flashes quickly
A -
N.B.: Max 3 W. If warning lights are in excess, the control panel processes will be endangered
with possible stop of all operations.
OPERATION AFTER BLACK-OUT (WITHOUT BATTERIES)
At the time of the blackout, gate status is saved in the memory.
When mains voltage is restored:
If the gate is located on the opening or closing limit switch, operating the control will close or
open the gate with the saved data.
If the gate is in intermediate position, operating the control will open the gate slowly until
it reaches the opening limit switch. After completing this first movement, the operator will
resume work at the set speed.
TECHNICAL SPECIFICATIONS
- Temperature range
- Humidity
- Power supply
- Frequency
- Transformer power
- Maximum absorption
- Power supply microinterruptions
- Maximum power SIGNAL output
- Flasher maximum load
- Current available for photocells and accessories 24 Vdc 500 mA ±15%
- Battery power supply
RADIO TECHNICAL SPECIFICATIONS (model L1 24V-CRX)
- Reception frequency
- Impedence
- Sensitivity
- Feedback control
- Memory storage (codes)
- All inputs must be used as clean contacts because the power is generated internally (secure
power) to the board and is set up to ensure compliance with double or reinforced insulation
with regard to dangerous voltage.
- Any external circuits connected to the outputs of the control panel must be made in such
a manner as to ensure compliance with double or reinforced insulation with regard to
dangerous voltage.
- All inputs are controlled by a programmed integrated circuit that performs a self check every
time it starts operating.
TROUBLESHOOTING
After making all the connections, carefully following the diagram and having placed the gate
in intermediate position, check the correct lighting of led DL4, DL5, DL6, DL7, DL8, DL9, DL10
and DL16.
If one of the led does not turn on, check the following and replace any faulty components if
necessary (perform the inspection with the gate always in intermediate position):
DL4
DL5
DL6
DL7-8
DL9-10
DL13
DL16
During operation, hold DIP 1 su ON position, make sure that when the gate opens, the green led
DL2 turns on and that when the gate closes, red led DL3 turns on.
Otherwise, perform a new full opening programming sequence.
On the board there are resettable fuses which intervene in the event of a short circuit,
interrupting the output assigned to them.
In the event of troubleshooting, it is advisable to disconnect all the removable connectors and
insert them one at a time in order to more easily identify the cause of the fault.
37
red
OFF limit switch that stops gate closure is faulty
green OFF limit switch that stops gate opening is faulty
red
OFF stop button fault (if the STOP is not connected, run the jumper between
COM and STOP).
red
OFF photocell fault (if the photocells are not connected, run the jumper
between COM and PHOT 1/PHOT 2).
red
OFF safety edge fault (if the edge is not connected, run the jumper between
COM and EDGE 1/EDGE 2).
blue
ON Some functions are enabled via smartphone, so via smartphone check
the card functions as the dips/trimmers status may not be true.
red
OFF manual release open (close it to restore the operation)
-10 ÷ +55°C
< 95% without condensation
230V~ ±10% (120 V 60Hz on request)
50/60 Hz
150VA - main 230Vac - 24Vac/10Vac
130 mA
100 ms
24 Vdc 3 W
24 Vdc 20 W
24 Vdc
433,92MHz
52 ohm
>1 µV
PLL
1000
G
B