6. TROUBLESHOOTING

After performing the user troubleshooting checks:
The control unit does not switch
on
Alternating voltage failure alarm
A battery voltmeter shows no
voltage
Internal battery charger alarm
(alarm LED on)
Internal battery charger off
(LEDs off)
With the selector switch in MAN
position and the START button
depressed, the motor pump
does not start
With the selector switch in AUTO
position and the start contact
active the motor pump does not
start
Batteries partially charged: check and recharge the
batteries; replace them if necessary.
QU3 fuse carrier open or blown fuse: check the fuse carrier
and, if necessary, replace the fuse
Connections to battery terminals corroded or loose: clean,
examine and tighten the nuts on the battery terminals.
Replace the cable terminals and nuts if they are too
corroded
Line power failure: check the line wire and voltage.
QU1 fuse carrier open or blown fuses: check the fuse
carrier and, if necessary, replace the fuses
Battery disconnected: Connections to battery terminals
corroded or loose: clean, examine and tighten the nuts on
the battery terminals. Replace the cable terminals and nuts
if they are too corroded.
Install a new battery if not present.
Reversed polarity: disconnect the battery and reconnect
properly
Battery disconnected: Connections to battery terminals
corroded or loose: clean, examine and tighten the nuts on
the battery terminals. Replace the cable terminals and nuts
if they are too corroded.
Install a new battery if not present.
Shorted terminals: replace the battery or, if it is still
efficient, restore the connections.
Battery voltage value too low: replace the battery
Line power failure: check the line wire and voltage
QU1 fuse carrier open or blown fuses: check the fuse
carrier and, if necessary, replace the fuses
Starting relay blown
Batteries discharged or disconnected: Connections to
battery terminals corroded or loose: clean, examine and
tighten the nuts on the battery terminals. Replace the
cable terminals and nuts if they are too corroded.
Install a new battery if none is present or if the one being
used is discharged
Both starting relays blown
Control unit failure
Batteries discharged or disconnected: Connections to
battery terminals corroded or loose: clean, examine and
tighten the nuts on the battery terminals. Replace the
cable terminals and nuts if they are too corroded.
Install a new battery if none is present or if the one being
used is discharged
Both starting relays blown