5. ELECTRICAL PANEL CONTROL TERMINALS
X1 - ANALOGUE AND DIGITAL INPUT TERMINALS
CODE
DESCRIPTION
B1+
Analogue signal input for battery 1 voltage value
B2+
Analogue signal input for battery 2 voltage value
B-
Common input for battery negatives and others
AV1
Starting relay 1 command output
AV2
Starting relay 2 command output
STOP
Engine shut-off device command output
"Low Engine Oil Pressure" signal input. The input is enabled by the controller
BPO
10 seconds after the engine has been started
"High Engine Temperature" signal input. The input is enabled by the
ATA
controller 10 seconds after the engine has been started
IN RIS.
"Low Fuel Level" signal input
CB
Battery charger voltage input from engine
PK
Frequency signal input (PICK-UP) for engine speed measurement
PK-
PICK-UP reference (ground)
PRESS-
Pressure switch start contact signal reference (ground)
PRESS
Pressure switch start contact signal input
IN AUX1
Digital signal input active, programmable from set-up
IN AUX2
Digital signal input active, programmable from set-up
Digital signal input active, programmable from set-up. Available directly on
IN AUX3
electronic control unit terminal board
Alternating power supply voltage input for panel internal devices. Phase,
QF1
neutral and ground (yellow/green) cables must be connected to
corresponding PE terminal
QU2
Alternating power supply output for engine heating device HEATER
RS232 connector for connection to PC (or similar) for event memory transfer
RS232
or download via a dedicated software
Note: For terminal numbering see diagram attached to electrical panel
43