INFORMATION FOR INSTALLERS AND USERS
1. ELECTRONIC MOTOR PUMP CONTROL UNIT

ELECTRICAL CHARACTERISTICS

-
Selectable 12Vdc or 24Vdc battery power supply
-
Operating range 6 ÷ 35Vdc
-
Stand-by power consumption (display illumination On) 350mA
-
Stand-by power consumption (display illumination Off) 230mA
-
Maximum power consumption 3A
-
Dry contact output, contact capacity 5A, 277Vac – 10A, 125Vac (current limitation
is provided by the capacity of the common circuit of all the control unit outputs)

MECHANICAL CHARACTERISTICS

-
Aluminium casing measuring 205x150x50 mm (WxHxD)
-
Extractable terminal blocks, polarized as follows:
One 16-pin male terminal block for inputs
One 12-pin male terminal block for outputs
-
RS232 connector for communication port
-
Standard front panel protection class: IP54
-
Terminal blocks protection class: IP20
-
Storage ambient temperature from -10°C .. to +70°C
-
Operating ambient temperature from -10°C .. to +50°C
-
Maximum humidity: 20%..85%, provided no condensation occurs