X1 – STATUS RELAY TERMINALS
CODE
DESCRIPTION
OUT AUX1
Output activated by alarm programmed from set-up
OUT AUX2
Output activated by alarm programmed from set-up
OUT RIS.
Output activated if "IN RIS." input is connected to ground
Alarm summary output. Output activated by at least one of the following
alarms:
- Automatic operation disabled
- Engine running
- MP06 control board fault
- Engine failure to start
- Low fuel level
- Low engine oil pressure
ALARM
- High engine temperature
- No AC voltage
- Low Battery 1 or 2 voltage
- Low engine rpm
- Engine overspeed (runaway)
- Triggering of Heater and/or Battery charger protection
- Input signal IN AUX1
- Input signal IN AUX2
- Input signal IN AUX3
- Fuel reserve
NO AUTO
Output activated by Selector switch not in Automatic mode position
NO START
Output activated in case of failure of 6 automatic attempts to start engine
MOTOR ON
Output activated by engine running status
Output activated by control unit alarm for:
FAULT NC
- software alarm
- hardware alarm
FAULT NO
- No Vdc power supply voltage alarm
NO contact available on control unit terminal board
COM
Relay outputs common
44