5

Troubleshooting and fault elimination

5
Troubleshooting and fault elimination
In the case of a fault, the letter
indicated on the 7−segment display of the card module.
Card module
Display
Text
E 1
Stop drive
(T1 for 3 s)
E 2
Check card
38
E
(for "Error") and an error code (
Cause
IEC 61131 program not stopped or
controller inhibit not set
Memory card is missing or not
inserted correctly
Memory card is write protected
Memory card is not supported
All data records on the memory
card are defective (e.g. because of
mains disconnection or pulling
out the card module during an
upload)
l
1
8
F
...
or
) are alternately
Remedy
Press key T1 for at least 3 s.
l
The drive stops ("PLC stop")
and the set exception
handling response (Lenze
setting: TRIP) is activated.
After 10 s (the 7−segment
display is counting down from
9 to 0 in steps of 1 s) the
controller inhibit is set.
l
You can abort by pressing any
key. (The set exception
handling response remains
active.)
Note:
You cannot abort by pressing key
T1 when AIF write protection is
activated in the basic device
(C0096/1 = 2).
Insert memory card correctly
(^ 34).
SD card: move slide switch to
"unlock" position.
Use supported memory card
(^ 30).
Delete all data records on the
memory card with the program
"Card File Handler", so that the
memory card can be written to
again afterwards.