- Set the bypass set-point temperature (default value
21°, shown on display) according to the mode being
used by the infrared remote control and as follows:
SET key.
- Set the minimum and maximum speeds (default
setting is 2000 rpm, value shown on display = 46)
according to the mode being used by the remote
control unit and as follows: SET key.
(NB: not all the functions on the remote control refer to
the appliance)
SET key (fig. 25)
25
25
DISPLAY
SET
Sets the following parameters. To move from one
parameter to the next, press NEXT.
Temperature setting (fig. 25a):
25a
25a
• view the parameter on the remote control by pressing
the following keys: SET, NEXT (several times);
• set the value of the flashing field with the + and - keys;
the sequence will be: C/F (unit of measurement, °C for
degrees Celsius, F for degrees Fahrenheit), internal T
value (from 15°C to 30°C, in steps of 1°C).
12
AUTO
Su
TIMER MODE
NEXT
ENTER
°C
V min setting (fig. 25b):
25b
25b
• set speed level 1 using the control box selector
switch;
• view the parameter on the remote control by
pressing the following keys: SET, NEXT (several
times);
• set the value of the flashing field with the + and -
keys (from 0 to 69 step 1); Press ENTER or NEXT to
confirm. The display will switch to the V max setting.
V max setting (fig. 25c):
25c
25c
• set speed level 3 using the control box selector switch;
• view the parameter on the remote control by pressing
the following keys: SET, NEXT (several times);
• set the value of the flashing field with the + and - keys
(from V min +10 to 99 step 1); Press ENTER or NEXT to
confirm. The display will switch to the main screen.
NOTE
The best energy efficiency class for the appliance is
obtained by setting one of the three speeds,
minimum, maximum or medium (calculated by the
system as mid way between minimum and
maximum), to "62".
Individual motor adjustment procedure: The revs can
be set to minimum or maximum speed for each
individual motor. Please refer to the remote control
instruction manual for details on how to enable this
function.
Use of the remote control will also allow the system to
be diagnosed. The following errors will be displayed:
ER01: by-pass/de-frosting valve blocked
ER02: motor driving outside air intake fan blocked
ER03: motor driving stale air exhaust fan blocked