Function Multifunction Key (Mp-Key) And Multifunction Inputs (Mp-Inp) - Kübler CODIX 566 Mode D'emploi

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

9.4
Function Multifunction Key
(MP-Key) and Multifunction
inputs (MP-INP)
Tare
In the function group MP.KEY, programme the
function TARA to ON. In the operating mode
select the current measured value (ACTUAL)
and briefly press the MP Key.
In the function group MP.INP, programme the
function MP.INP1 or MP.INP2 to TARA. In the
operating mode briefly activate the
multifunction input 1 or multifunction input 2.
Reset Tare Value
• In the function group MP.KEY, programme the
function TARA to ON. In the operating mode
select the current measured value (ACTUAL)
and press the MP Key >5 sec.
• In the function group MP.INP, programme the
function MP.INP1 or MP.INP2 to R.TARA. In
the operating mode briefly activate the
multifunction input 1 or multifunction input 2.
Reset MIN value memory
• In the function group MP.KEY, programme the
function RES.MIN to ON. In the operating mode
select the minimum value memory (MINIMU)
and briefly press the MP Key.
• In the function group MP.INP, programme the
function MP.INP1 or MP.INP2 to RES.MIN or
R.PEAKS. In the operating mode briefly
activate the multifunction input 1 or
multifunction input 2.
Reset MAX value memory
• In the function group MP.KEY, programme the
function RES.MAX to ON. In the operating
mode select the maximum value memory
(MAXIMU) and briefly press the MP Key.
• In the function group MP.INP, programme the
function MP.INP1 or MP.INP2 to RES.MAX or
R.PEAKS. In the operating mode briefly
activate the multifunction input 1 or
multifunction input 2.
Reset of relay outputs in Latch mode
• In the function group MP.KEY, programme the
function RES.REL to ON. In the operating mode
briefly press the MP Key.
• In the function group MP.INP, programme the
function MP.INP1 or MP.INP2 to RES.REL. In
the operating mode briefly activate the
multifunction input 1 or multifunction input 2.
Adopt new measured value for Totaliser
• In the function group MP.KEY, programme the
function ACK.TOT to ON. In the operating
mode select the totaliser (TOTAL) and briefly
press the MP Key.
• In the function group MP.INP, programme the
function MP.INP1 or MP.INP2 to ACK.TOT. In
the operating mode briefly activate the
multifunction input 1 or multifunction input 2.
Reset Totaliser
• In the function group MP.KEY, programme the
function RES.TOT to ON. In the operating
mode, select the totaliser (TOTAL) and briefly
press the MP Key.
• In the function group MP.INP, programme the
function MP.INP1 or MP.INP2 to RES.TOT. In
the operating mode briefly activate the
multifunction input 1 or multifunction input 2.
Display Hold
• In the function group MP.INP, programme the
function MP.INP1 or MP.INP2 to DISP.HD. In
the operating mode, select either the current
measured value (ACTUAL) or the totaliser
(TOTAL) and activate multifunction input 1 or
multifunction input 2.
Lock-out Limit Value (Alarm) setting
• In the function group MP.INP, programme the
function MP.INP1 or MP.INP2 to LOC.ALR. In
the operating mode, activate multifunction input
1 or multifunction input 2.
Lock-out Programming and Default
setting
• In the function group MP.INP, programme the
function MP.INP1 or MP.INP2 to LOC.PRG. In
the operating mode, activate multifunction input
1 or multifunction input 2.
Lock-out Keypad
• In the function group MP.INP, programme the
function MP.INP1 or MP.INP2 to LOC.KEY. In
the operating mode, activate multifunction input
1 or multifunction input 2.
Page 13

Publicité

Table des Matières
loading

Table des Matières