Swinger Shutdown; Hardware Default - Johnson Controls tyco 3G4000W Manuel D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Table 8: Reporting codes
Reporting code
Periodic Test
Periodic Test with
Trouble
Radio Activation
Internal Buffer Full
Failure to
Communicate Restore
Firmware Update
Successful
Firmware Update Fail
Firmware Update
Begin
Tamper Trouble
Tamper Trouble
Restore

Swinger shutdown

The swinger shutdown feature protects against runaway signals to the central station by limiting
certain trouble or alarm events to a maximum of three reports every 24 hours. The system restores
the condition at midnight and may report the signals again. The swinger shutdown feature limits
the number of events that the system logs to the cummunicator's event history. The event history
also creates a log entry when the swinger shutdown feature occurs or clears for each event.
You can apply the swinger shutdown feature to the following conditions:
• System tamper and restore
• Battery trouble and restore
• PSTN line down and restore
• Input power trouble and restore
• FTC restore
• Zone input alarm and restore

Hardware default

The hardware default feature erases any programme information and restores the product to the
default settings. After the system performs a hardware default, you must reprogramme the system
using the DLS software. The DLS software fully programs all the options that the product contains.
Note: The hardware default feature is optional for the 3G4000W.
18
Contact ID
E603-XXX
E608-XXX
R552-000
E624-000
R354-000
R901-000
E902-000
E901-000
E145-000
R145-000
3G4000W 3G (HSPA) WIRELESS ALARM COMMUNICATOR INSTALLATION MANUAL 5.0
SIA
RP-XXX
RY-XXX
RS-000
JL-000
YK-000
LS-000
LU-000
LB-000
ES-000
EJ-000
Notes
Test transmission
<Receiver Path>
Test translation
<Receiver Path>
Remote programming
successful
Communications
trouble restored
Case or wall tamper
Case or wall tamper
restore