Warning And Error Messages During Guided Commissioning - BONFIGLIOLI Vectron ACTIVE ACT 201 3,0 Guide De Démarrage Rapide

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Code
F08
01
Electronics voltage too low, check control terminals.
04
Electronics voltage too high, check wiring of control terminals.
F11
00
Output frequency too high, check control signals and settings.
01
Max. frequency achieved by control, check deceleration ramps and connected brake resistor.
F13
00
Earth fault on output, check motor and wiring.
10
Minimum current monitoring, check motor and wiring.
F14
01
Reference value signal on multifunctional input 1 faulty, check signal.
07
Overcurrent on multifunctional input 1, check signal.
6.2

Warning and error messages during Guided commissioning

Code
SA000
No warning message present. This message can be read out via an optional communication module.
SA001
The value of the parameter
verter. The maximum reference voltage is indicated on the nameplate of the frequency inverter.
SA002
The calculated efficiency is in the limit range for a three-phase motor. Check the values entered for the
Rated Voltage
parameters
SA003
The value entered for parameter
Check the value.
SA004
The calculated slip for an asynchronous motor is in the limit range.
Check the values entered for parameters
Code
SA0021
The stator resistance or rotor resistance is very high. The following causes are possible:
SA0022
The motor cable cross-section is not sufficient.
The motor cable is too long.
The motor cable is not connected correctly.
The contacts are not in a proper condition (corrosion).
SA0041 The slip speed was not determined correctly. Check the values entered for parameters
Rated Frequency
372 and
SA0042 The slip speed was not determined correctly. Check the values entered for parameters
Rated Frequency
372 and
SA0051 The machine data for star connection were entered, the motor, however, is connected in delta. For star
operation, change the motor cable connection. For delta operation, check the entered rated motor val-
ues. Repeat the parameter identification.
SA0052 The machine data for delta connection were entered, the motor, however, is connected in star. For
delta operation, change the motor cable connection. For star operation, check the entered rated motor
values. Repeat the parameter identification.
SA0053 A phase asymmetry was measured. Check the cables at the terminals of the motor and the frequency
inverter for proper connection and check the contacts for corrosion.
06/07
06/07
Electronics voltage
Output frequency
Motor connection
Control connection
Warning messages during Guided commissioning
Meaning / Remedy
Rated Voltage
370 is out of the rated voltage range of the frequency in-
Rated Current
370,
Rated Cosinus Phi
Rated Speed
Warning messages after Parameter identification
Meaning / Remedy
375.
375.
Meaning
Rated Mech. Power
371 and
374 is outside of the normal range (0.6 to 0.95).
Rated Frequency
372 and
376.
375.
Rated Speed
Rated Speed
35
35

Publicité

Table des Matières
loading

Table des Matières