Electrical Installation; Emc Information - BONFIGLIOLI Vectron ACTIVE ACT 201 3,0 Guide De Démarrage Rapide

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

2

Electrical Installation

Danger!
When the frequency inverter is disconnected from power supply, the mains, DC-link voltage and
motor terminals may still be live for some time. Wait for some minutes until the DC link capaci-
tors have discharged before starting to work at the unit.
The unit may only be connected with the power supply switched off.
Make sure that the frequency inverter is discharged.
2.1

EMC Information

T he frequency inverters are desi g ned for operation in industrial applications. Electroma g netic interference can be
avoided by the following precautions:
Install the frequency inverters and commutating chokes on a metal mounting panel. Ideally, the mounting
panel should be galvanized.
Provide proper equipotential bonding within the system or the plant. Plant components such as control cabi-
nets, control panels, machine frames, etc. must be connected by means of PE cables.
Connect the frequency inverter, the commutating choke, external filters and other components to an earthing
point via short cables.
Keep the cables as short as possible and avoid sagging cables for installation.
Contactors, relays and solenoids in the electrical cabinet are to be provided with suitable interference suppres-
sion components.
The mains connection cable must be installed separate from the control, data and motor cables.
Connect the shield of the motor cable to ground potential properly on both sides by using shield clamps.
Connect the shield of the control cables to ground potential properly on both sides.
06/07
06/07
23
23

Publicité

Table des Matières
loading

Table des Matières