Fuel Supply; Gas Train - Riello RX 180 S/PV Instructions D'installation, D'utilisation Et D'entretien

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Gas valve
Gas
pressure
test point
upline (P1)
Compensation pipe (T)
+
-
(A)
4
F
1
2
3
P1
L1
(B)
Maximum flow adjustment (V1)
Downstream pressure test point (P2)
+
-
Metal protection
Minimum gas flow
adjustment on the stabiliser (V2)
5
VS
R
VR
P2
L
Air/gas mixer
(Venturi)
in the suction
circuit
Compensation pipe (T)
Wiring loom fitting
D7803
D8668
8

FUEL SUPPLY

The burners are teamed with one-piece pneu-
matic proportioning gas valves, via which the
amount of gas delivered, and hence the output
produced, can be modulated.
A signal reporting pressure detected in the air
circuit is carried to the pneumatic gas valve,
which delivers an amount of gas in proportion to
the airflow produced by the fan.
The gas train, in order to render the dimensions
efficent is assembledd directly onto the burner
body.
Air/gas mixer
Gas and combustive air are mixed inside the
purging circuit (mixer), starting from the intake
inlet. Through the gas train, fuel is introduced
into the intake air current and optimal mixing
commences with the aid of a mixer.
Note
The pipe (T) between Venturi-valve, accidental
blocking of the intake can be compensated by
reducing the amount of gas delivered.
After connecting the compensation pipe (T),
with the valve coat it with a rubber protection.
GAS TRAIN (B)
Approved, together with the burner, according to
the regulation EN 676, and supplied.
LEGENDA (B)
1 - Gas input pipe
2 - Manual valve
3 - Vibration damping joint
4 - Pressure gauge with pushbutton cock
5 - Valve, including:
- filter (replaceable)
- working valve
- pressure adjuster
P1 - Pressure up-line from the filter
P2 - Downstream pressure of valve
L - Gas train supplied
L1 - The responsibility of the installer

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Rx 250 s/pv3790310379033037903003790320

Table des Matières