Installer Setting - Setting Temperature Range - LG PREMTB10U Manuel D'installation Et D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Installer Setting – Setting temperature range
This function is used to select the temperature range options.
In case of the setting temperature range option2( 31:01), please note that the setting of the re-
mote controller (with cable) can be altered under below circumstances.
- In case of cooling at 30~37.5 °C(64~99 °F), it is changed to cooling at 86 °F(30 °C).
- In case of heating at 4~15.5 °C(40~86 °F), it is changed to heating at 60 °F(16 °C).
- If it is on the 2Set Mode, it is changed to the current operation mode(cooling or heating) of the
indoor unit.
Situation where changes in the setting occur
a. Operates the Auto address work and pipe search in situations such as product installment and
service.
b. Occurrence of errors and deactivation.
c. Command generated by the central control, outdoor unit, Dry contact, Remote controller, in-
door unit switch.
INSTALLATION INSTRUCTIONS
Press the
button for 3 second to
1
enter Thermostat installer setup
mode.
- If pressed for a shorter time, it
enters into user setup mode.
2
Press
button to select Function
code 31.
3
Select Temperature
range by pressing
buttons.
00(option1):
60~86 °F / 16~30 °C (default)
01(option2):
40~99 °F / 4~37.5 °C
Press
button to save or
4
release.
When the set values are changed,
the items below will be initialized.
- Setting temperature
(default: Cooling: 86 °F(30 °C)/ Heating: 60 °F(16 °C))
- Set back temperature
(default: Cooling: 86 °F(30 °C)/ Heating: 60 °F(16 °C))
-Weekly Reservation
5
Press
button to exit or system
will automatically exit after 25
seconds without any input.
83

Publicité

Table des Matières
loading

Table des Matières