LG PREMTB10U Manuel D'installation Et D'utilisation page 69

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Installer Setting - E.S.P. Function
This function determines the fan speed strength setting for each level (low, med, high).
• If you set ESP incorrectly, the air conditioner may malfunction.
• This setting must be carried out by a certificated-technician.
Function code,
ESP code
ESP value
• ESP settings vary between different product types.
INSTALLATION INSTRUCTIONS
Press the
button for 3
1
seconds to enter Thermostat
installer setup mode.
- If pressed for a shorter time, it
enters into user setup mode.
If entering into ESP setup mode by using
2
button, it indicates as the picture
below.
3
Select ESP fan step by pressing
buttons. (01: very low, 02: low,
03: medium, 04: high, 05: very high)
Move to ESP value setting by pressing
4
button.
(000 is the factory
default setting.)
5
Press
buttons to setup ESP value.
(It is possible to setup ESP
value from 1 to 255, and 1 is
the smallest and 255 is the
largest).)
69
ESP step
Function Code
ESP value

Publicité

Table des Matières
loading

Table des Matières