1.29 Pump rotation interval
Time of daily change in the pump starting
order.
0h: No change.
1-24h: Change according to the set time.
25h: Change at each restart or by remote
control.
1.30 Ramp start
Set in seconds of time alignment of the set
pressure set by the run command.
IF CONTROL PANEL WITH
INVERTER SINCE 24A OR HIGHER,
SET AT 5 s
1.31 Running hours.
Page displaying the total running hours of the motors.
1.32 Starts per hour
Maximum threshold starts in an hour.
0: Alarm disable
1-60: Max number of starts per hours
1.33 Setting default
Page to restore the default data in all parameters of the board.
To restore the data press simultaneously the buttons 'increase' and 'decrease'.
0 - 25 h
000 - 300 sec
0 - 60
44
25 h
001 s
(005 s)
0