EBARA 2SP MFC 1,5T-2 Instructions Pour L'installation Et La Maintenance page 40

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

CONFIGURATION HOME
PAGE MENU
Visualization
ENGLISH
Submenu SET PLANT
Viewing page of the configuration menu.
1: Set plant
2: Set inverter
3. Set inputs outputs
4: Managing Alarms
5: Electrical values
6: Software version
Submenu SET IMPIANTO – FREE ACCESS
Description
1.1 Reference pressure 1
Pressure set-point in bar, to be kept constant.
1.2 Reference pressure 2
Pressure Setpoint 2, to be kept constant,
with reference to the remote control R.C.
Page active only if is set "Change P. Set"
for the digital input (3.1)
1.3 KP correction
Instantaneous correction of error of the
system instantaneous pressure and the
reference pressure.
IF CONTROL PANEL WITH
INVERTER SINCE 24A OR HIGHER,
SET AT 10
1.4 KI correction
Integral part of the error between the
reference pressure and the real pressure.
1.6 Pump rated pressure
Pump rated pressure in bar, at 0 litres and at
50 Hz.
Page active only plants stopped.
1.7 Pressure Transducer full-scale
Full-scale value of the pressure transducer in
bar.
Page active only plants stopped.
1.8 Motors Thermal Protection
Threshold of intervention for reached current
limit, on Motors
Page active only plants stopped.
Field
00.0 - 25.5 bar
00.0 - 25.5 bar
000 - 250
000 - 250
000.0 - 025.5 bar
0.0 - 25.0 bar
0.0 - 61.0 A
40
Default
00.0 bar
00.0 bar
050
(010)
050
010.0 bar
10.0 bar
0 A