PNEUMATIC INSTALLATION

The control valve is driven by compressed air via the Top Control .
Connect the air supply to port 1
The supply pressure required for complete opening or closing of the valve may lie between the minimum values of 3 to 6 bar,
depending on the drive unit. The permissible maximum value for the control pressure is 7 bar. The value for the supply pressure is
given as P
on the rating plate of the respective valve.
pilot
Mount the exhaust air pipe or noise reducer on port 3
Control medium:
Fluidic connections of the Top Control Continuous
Supply pressure connector
(inscription: 1)
Type 2700
instrument air, class 3 according to DIN ISO 8573-1
Outlet air
connector
(inscription: 3)
C
OMMISSIONING
CO 3