WATER CONNECTION -- CNV14E ONLY
NOTE: Hot water maximizes steam production but
is not required. Cold water may be supplied
to both inlets if hot water is not available.
Connect the appliance to quality water via a pres-
sure hose with 3/4" (19mm) couplings. See
Figure 6 for connections. A shut off valve is to be
provided adjacent to the oven.
WARNING!!
Operating the appliance without the water
regulator installed will invalidate your war-
ranty.
Water must meet the following minimum require-
ments:
Total Dissolved Solids (TDS) content will not ex-
D
ceed 30 parts per million.
Water PH must be 7.0 or higher
D
WARNING!!
The use of poor quality water will invali-
date your warranty.
CNV-14E
Cold
Water
Water Connections
Rear of Appliance
Figure 6
DRAIN CONNECTION
The steam vent assemblies are constructed of 2"
DWV copper piping reduced to 1-1/2 DWV pipe. If
the vent system is not purchased as an option
(R9381), Blodgett Combi recommends plumbing
the oven as shown in Figure 7.
The steam vent should be run to an open floor
drain avoiding flexible hose that could sag and al-
low trapped water to accumulate. The customer
must supply the piping from the oven to the drain.
Connect the drip pan drain to the steam vent with
1.125 I.D. hose.
Use the drain vent assembly and a 2" (50.8mm)
pipe for drain connection.
Specific water/drain connection for City of Los
Angeles
1. Each drain line from the appliance shall be
routed without dips or sags to terminate
above the flood level rim of an approved indi-
rect waste receptor.
2. The appliance shall be installed in accordance
with the manufacturer's printed instructions
and the LAPC and LAMC, 1999 editions.
3. A backflow protection device shall be installed
on the potable water system directly ahead of
the appliance. The backflow protection device
shall be any of the following: an approved pres-
sure type vacuum breaker installed at least 12"
above the highest point of use, a double check
valve backflow preventer or a reduced pressure
principal backflow preventer.
9
Installation

Plumbing Connections

Coupling
Customer supplied
2" (50.8mm) drain
waste vent piping
Figure 7