Step Three: Make Add-On Air Proving Decision - Honeywell TrueSTEAM Guide D'installation

Masquer les pouces Voir aussi pour TrueSTEAM:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

STEP THREE:
Make Add-On Air Proving Decision
In addition to monitoring system power and fan regulation, TrueSTEAM can monitor physical air movement
through an optional add-on air proving device. If an air proving device is added, TrueSTEAM can create steam
only if the fan is moving air through the supply duct.
Note: This image is not a complete wiring diagram. It only depicts add-on air proving.
See "Wiring the TrueSTEAM" on page 19.
TrueSTEAM
R
C
1
2
3
4
5
On
Off
18
R
C
6
WIRING BASICS
Wire TrueSTEAM R and C to HVAC system
HVAC System
R and C with an air proving device in-line
on C.
Configure air proving through DIP 5 on
TrueSTEAM. Set DIP 5 up and keep
DIP 4 down.
TrueSTEAM will look for physical air
movement through its C connection before
steam enters the duct.
M29619
TrueSTEAM Humidification System 69-2285EF—01

Publicité