5. Commissioning, operation
Relationship between power supply and load (R
EN
5.2.2 Making the electrical connection
Screw the connector in hand-tight. The ingress protection is only ensured if the installation
instructions for the seals are followed.
Ensure that no moisture can enter at the cable end.
The transducer must be grounded via the process connection.
Use a shielded cable, if the line is longer than 30 m or leaves the building.
Do not connect the cable shield on the instrument side.
16
4 ... 20 mA, 3-wire
permissible range
WIKA operating instructions Ultra High Purity transducer, model WUD-2x
)
A
Current output (3-wire)
4 ... 20 mA:
R
A
Voltage output (3-wire)
DC 0 ... 5 V: R
DC 0 ... 10 V: R
with R
U+
≤ (U+ – 10 V) / 0.02 A
> 5 kΩ
A
> 10 kΩ
A
in Ω and U+ in Volt