Short Circuit rating F5/F6 housing H:
240V Models:
"Suitable For Use On A Circuit Capable Of Delivering Not More Than 18000 rms Symmetrical
Amperes, 240 Volts Maximum When Protected by Class RK5 Fuses.
See instructional manual for maximum fuse sizes"
480V Models:
"Suitable For Use On A Circuit Capable Of Delivering Not More Than 18000 rms Symmetrical
Amperes, 480 Volts Maximum When Protected by Class RK5 Fuses.
See instructional manual for maximum fuse sizes"
Branch Circuit Protection of inverters F5/F6 housing H:
UL 248 Fuses; Class RK5 as specified below
Inverter
15F5/F6
16F5/F6
17F5/F6
15F5/F6
16F5/F6
17F5/F6
18F5/F6
19F5/F6
20F5/F6
The voltage rating of the fuses must at least equal to the input voltage of the inverter (or simi-
lar wording).
F - 36
Input
Voltage [V]
240 / 3ph
240 / 3ph
240 / 3ph
480 / 3ph
480 / 3ph
480 / 3ph
480 / 3ph
480 / 3ph
480 / 3ph
UL 248 Fuse
class RK5 or J [A],
maximum rating
70
90
110
40
50
60
70
90
100