Mitsubishi Electric ecodan EHPT Série Manuel D'installation page 31

Masquer les pouces Voir aussi pour ecodan EHPT Série:
Table des Matières

Publicité

7
Service and Maintenance
Engineers Forms
Commissioning/Field settings record sheet (continued from the previous page)
Main remote controller screen
Setting
Service menu
Pump speed
Heat source setting
Heat pump setting
Operation
settings
DHW
Heating/Cooling
Heat pump flow rate range Minimum(0 - 100 L/min)
Quiet mode
Heating operation
Flow temp.range
*8
*10
Room temp.control
*14
Heat pump thermo
diff.adjust
Freeze stat function *11
Simultaneous operation (DHW/Heating)
Cold weather function
Boiler operation
Smart grid ready
DHW
Heating
Cooling
Pump cycles
Floor dry up function
Summer mode
Water flow control
Parameters
Pump speed(1 - 5)
Pump speed(1 - 5)
Standard/Heater/Boiler/Hybrid *7
Maximum(0 - 100 L/min)
Day (Mon - Sun)
Time
Quiet level (Normal/ Level1/ Level2)
Minimum.temp.(20 - 45°C)
Maximum.temp.(35 - 60°C)
Mode(Normal/Fast)
Interval(10 - 60 min)
On/Off *6
Lower limit(−9 - −1°C)
Upper limit(+3 - +5°C)
Outdoor ambient temp. (3 - 20°C) / **
On/Off *6
Outdoor ambient temp. (−30 - +10°C) *3
On/Off *6
Outdoor ambient temp. (−30 - −10°C) *3
Hybrid settings
Outdoor ambient temp.
(−30 - +10°C) *3
Priority mode (Ambient/Cost/
CO
2) *16
Outdoor ambient temp. rise
(+1 - +5°C)
Intelligent set-
Energy
Electricity
tings
price
(0.001 - 999 */kWh)
*9
Boiler
(0.001 - 999 */kWh)
CO
Electricity
2
emis-
(0.001 - 999 kg -CO
sion
kWh)
Boiler
(0.001 - 999 kg -CO
kWh)
Heat
Heat pump capacity
source
(1 - 40 kW)
Boiler efficiency
(25 - 150%)
Booster heater 1
capacity
(0 - 30 kW)
Booster heater 2
capacity
(0 - 30 kW)
On/Off
Target temp(+1- +20°C) / -- (Non active)
On/Off
Target temp.
Switch-on recommendation(20 - 60°C) 50°C
Switch-on command(20 - 60°C)
On/Off
Target temp.
Switch-on recommendation(5 - 25°C)
Switch-on command(5 - 25°C)
Heating (On/Off)
Cooling (On/Off)
Interval(10-120 min)
On/Off *6
Target temp.
Start&Finish (20 - 60°C)
Max. temp. (20 - 60°C)
Max. temp. period (1 - 20 days)
Flow temp.
Temp. increase step (+1 - +10°C)
(Increase)
Increase interval (1 - 7 days)
Flow temp.
Temp. decrease step (−1 - −10°C)
(Decrease)
Decrease interval (1 - 7 days)
On/Off
Outdoor ambi-
Heating ON (4-19°C)
ent temp.
Heating OFF (5-20°C)
Judgement
Heating ON (1-48 hours)
time
Heating OFF (1-48 hours)
Forced heating ON (-30 - 10°C)
On/Off
Default
Field
Notes
setting
setting
5
5
Standard
5 L/min
100 L/min
0:00 - 23:45
Normal
30°C
50°C
Normal
10 min
On
-5°C
5°C
5°C
Off
−15°C
Off
−15°C
−15°C
Ambient
+3°C
0.5 */kWh
0.5 */kWh
0.5 kg -CO
/kWh
2
/
2
0.5 kg -CO
/kWh
2
/
2
11.2 kW
80%
2 kW
4 kW
Off
--
Off
55°C
Off
15°C
10°C
On
On
10 min
Off
30°C
45°C
5 days
+5°C
2 days
−5°C
2 days
Off
10°C
15°C
6 hours
6 hours
5°C
Off
(Continued to next page.)