Wiring According To Emc - Lenze INTERBUS PT Instructions De Montage

Module de fonction
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Wiring according to EMC

For wiring according to EMC requirements observe the following points:
)
Note!
Separate control cables/data lines from motor cables.
ƒ
Connect the shields of control cables/data lines at both ends in the case of
ƒ
digital signals.
Use an equalizing conductor with a cross−section of at least 16 mm
ƒ
(reference: PE) to avoid potential differences between the bus nodes.
Observe the other notes concerning EMC−compliant wiring given in the
ƒ
documentation for the standard device.
Wiring procedure
1. Observe the bus topology, do not use any stubs.
2. Follow the wiring notes given in the documentation for the control system.
3. Only use cables which comply with the specifications listed (^ 49).
4. Observe the notes concerning the voltage supply of the function module (^ 50).
EDK82ZAFIC−010 DE/EN/FR 6.0
Electrical installation
Wiring according to EMC