3. Press scroll up
buzzer ON (as drawing Q1), or buzzer OFF (as drawing Q2, Alarm silence for UPS
Warning) and self-test OFF (As drawing R1) or self-test ON. (as drawing R2. UPS will
execute battery test for 10 seconds. If the self-test is successful, it will show as Drawing
E1; otherwise, it will show as drawing E2 & error message in the same time.)
3.5.5. UPS Default Settings and their alternatives
1. Make sure the UPS is not "On" yet. Press On Switch
simultaneously for approx. 3 seconds, the buzzer will sound twice, the LCD display
screen shows as drawing Q1, then the UPS is under setting mode now.
2. To scroll down the LCD screen, you may refer to Chapter 2
3. Except Buzzer (as drawing Q1 & Q2) and Self-test(as drawings R1 & R2), all the rest
default settings may be changed by pressing scroll up
4. Drawings S1 and S2 mean the bypass input acceptable window, it can be
184Vac~260Vac or 195Vac~260Vac.
5. Drawing T means the bypass frequency window of the Inverter Output, the acceptable
setting values are ±3Hz and ±1Hz.
6. Drawing U means the acceptable Inverter Output Voltage, of which voltage is 200Vac,
208Vac, 220Vac, 230Vac, or 240Vac.
7. Drawing V1, V2, V3 and V4 mean the operation modes of the UPS, of which alternative
is Online, Eco (Economic) mode, fixed 50Hz Output or fixed 60Hz Output.
8. Drawing W means the adjustments of the Inverter Output, which may be calibrated as
0%, +1%, -1%, +2%, -2%, +3%, or -3%.
9. Drawing X means a specified address & position of the UPS when the UPS is in Parallel
mode. The settable numbers are from 1st to 4th. The number must be 1st if the UPS is
not in parallel.
10. Drawing Y means the parallel function status. The "P 01" means parallel function
disabled and the "P 02" means parallel function enabled.
11. When all the setting changes are done, you have to press enter
the changes when the LCD screen shows as drawing Z, then, the LCD screen will show
as drawing AA to complete the setting changes. If you don't want to change those
settings, you may press "OFF"
to Drawing AA directly, which means your setting changes are invalid.
INFOSEC UPS SYSTEM – 4 rue de la Rigotière – 44700 Orvault – France – www.infosec-ups.com
49
Hot Line Tel : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 – hotline@infosec.fr – 11 11 AA 68 203 16
key pad, you may execute special functions. The Functions includes
key pads for 5 seconds, then the LCD screen turns
and scroll down
key pad.
key Pad to save all
key pads