Description; Posi-Bbpr (Gps) Models - VALPES DV 25 Manuel D'installation Et D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

EN
POSI-BBPR (GPS) : description
The GPS version includes BBPR and positioning
Battery position backup:
This system insure a return to predefined position in case of power failure. The predefined position can be set close
(default) or
open.
Positioning:
0-10 V : In case of outside event, absence of control signal (accidental wires cut for example) but in the presence of power,
the actuator will travel to defined position (open or closed valve). As standard our actuators will close themselves with absence
of control signal but there are other possibilities on request.
4-20 mA : In case of outside event, absence of setpoint signal (accidental wires cut for example) but in presence of power,
the actuator will stay in its position
The factory default configuration is "normally closed"
Actuator voltage
Battery voltage
Battery capacity
Charging current
Maximum battery charging time
Rep Terminals Description
B1
« Close » button
B2
« Mem» button
B3
« Open » button
C1
A,C
Motor connector
C2
67,68
Failure feedback relay
C3
65,66
Charging status feedback relay
F (+)
C4
F (-)
Battery connector
T (+)
17 (-)
C5
power supply connector
18 (+)
15(-)
Positioning setpoint signal con-
C6
16(+)
nector (0-10 V or 4-20 mA)
13A(+)
Positioning feedback signal
C7
13B(+)
connector.
14(-)
13A=0-10 V et 13B=4-20 mA
C8
A,0,B
RS485 connector
J1
CV1
Bluetooth
LED

Description

MANU manual / Bluetooth
HORO Weekly scheduler functioning mode
APPR Learning mode selected
POSI Positioning mode
DSBA3800 • Rév. 01/10/2020
function.
100 V to 240 V AC 50/60 Hz and 100 V to 350 V DC
24 V to 30 V AC 50/60 Hz and 24 V to 48 V DC
24 V DC
600 mAh
180 mA
3,5 h
®
activation jumper
®
functioning mode
Charging status feedback relay (65/66)
Failure feedback relay (67/68)
Temperature
C6
C7
LED
Description
Error detected:
 Timestamp memory empty/scheduler selected
 Clock failure
ERROR
 Excessive temperature
 Excessive torque
Power supply:
 Slow blinking (1 s) : charged battery
ACT
 Rapid blinking (0.5 s) : battery charging
APPR1
Open position stored (confirmation)
APPR2
Closed position stored (confirmation)
24 V DC - 1 A max
24 V DC - 3 A max
-10 °C à +40 °C
J1
C5
C4
C8
C3
C2
C1
LED
B1
B2
B3
43

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Dv 45Dv 75Dv 100Dv 150Dv 300

Table des Matières