BBPR (GS6) : description
Actuators with emergency unit (on-off wiring mandatory)
The BBPR models include an emergency battery unit controled by an electronic board. This system insure a return to predefi-
ned position in case of power failure. The predefined position can be set close (default) or open.
The BBPR actuators can be only on-off mode wired.
The factory default configuration is "normally closed"
Actuator voltage
Battery voltage
Battery capacity
Charging current
battery charging maximum time
Following a power failure,
the BBPR unit will reset
after 4 minutes
REP TERMINAL DESCRIPTION
17 (-)
C1
power supply connector
18 (+)
F (+)
C2
F (-)
Battery unit connector
T (+)
A
C3
B
Motor connector
C
D3
C4
1)
Failure feedback connector
D4
65
C5
1)
Charging feedback connector
66
A
C6
0
RS485 connector
B
J1
Bluetooth
®
activation jumper
1) The auxiliary cables must be connected to inside instal-
lation only
40
100 V to 240 V AC 50/60 Hz and 100 V to 350 V DC
24 V to 30 V AC 50/60 Hz and 24 V to 48 V DC
24 V DC
Charging status feedback relay (65/66)
600 mAh
Failure feedback relay (D3/D4)
180 mA
Temperature
3,5 h
C1
C2
C3
J1
LED

DESCRIPTION

Power supply:
 Slow blinking (1 s) : charged battery
ACT
 Rapid blinking (0.5 s) : battery charging
Error detected:
 Timestamp memory empty/scheduler selected
 Clock failure
ERROR
 Excessive temperature
 Excessive torque
HORO
Weekly scheduler functioning mode
MANU
manual / Bluetooth
WIRE
Electric wiring mode
EN
24 V DC - 1 A max
24 V DC - 3 A max
-10 °C to +40 °C
LED
C6
C5
C4
®
functioning mode
DSBA3800 • Rév. 01/10/2020