VALPES DV 25 Manuel D'installation Et D'utilisation page 41

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

EN
BBPR (GS6) : electric connection
Power supply and control wiring

Ensure that the voltage indicated on the actuator ID label corresponds to the voltage supply.

Unscrew the left cable gland and insert the cable.

Remove 25mm of the cable sheath and strip each wire by 8mm.

Connect the wires to the terminal strip in accordance with the diagram p. 42.

Tighten the cable gland (Ensure that it's well mounted to guaranty the proofness).
Position feedback wiring

Unscrew the right cable gland and insert the cable.

Remove 25mm of the cable sheath and strip each wire by 8mm.

Connect the wires to the terminal strip in accordance with the diagram p. 42.

Tighten the cable gland (Ensure that it's well mounted to guaranty the proofness).
Our actuators are equipped with two simple limit switch contacts normally set either in open position, either in closed
position. As per factory setting, the white cam is used to detect the open position (FC1) and the black cam is used to
detect the closed position (FC2).
The actuator is pre-set in our factory. Do not touch the two lower cams in order to avoid any malfunctioning or
even damage to the actuator.
Setting of end limit switches
To adjust the position of the auxiliary contacts, make rotate the two superior cams by using the appropriate wrench.
X
®
Thanks to A
MART
(via Bluetooth
that the actuator will reach in case of power failure.
it's also possible to access to actuator parameters in real time, to schedule weekly tasks
and to control it locally.
For any further information, refer to the operation manual with the reference DSBA3304.
DSBA3800 • Rév. 01/10/2020
®
connection), it's possible to set the backup position
41

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Dv 45Dv 75Dv 100Dv 150Dv 300

Table des Matières