VALPES DV 25 Manuel D'installation Et D'utilisation page 45

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

EN
POSI-BBPR (GPS) : electric diagram
POWER SUPPLY
N
Ph
-
+
1
2
TP/PE
100V-240V 50/60Hz (100V-350V DC)
24V-30V 50/60Hz (24V-48V DC)
1,2,3,4
Power supply terminal
67,68
Failure report Terminal (24V DC / 3A max)
A,0,B
RS485 terminal
13a,13b,14
Feedback signal terminal 4-20 mA (13b) or 0-10 V (13a)
In order to avoid electromagnetic perturbations, it is compulsory to use shielded cables (cables longer than
3m).
The control voltage must be S.E.L.V. (Safety Extra Low Voltage).
No common earth/ground connexion between the control (input and output signal) and the alimentation.
(Type 0-20 or 4-20mA : 5V DC max.)
10 kOhm input impedance if control with voltage (0-10 V) and 100 Ohm input impedance if control with cur-
rent (0-20 mA or 4-20 mA)
The card resolution is 1°
DSBA3800 • Rév. 01/10/2020
3
4
17
18
C
17
18
A
0
B
13a
13b
14
+
+
-
A
~
+
~
B
Motor
=
A
Charged battery :
contact closed
SNBA150000
67
68
4,5
Auxiliary limit switch 1 NO
6,7
Auxiliary limit switch 2 NO
65,66
Battery charging feedback terminal
15,16
Setpoint signal terminal 4-20 mA or 0-10 V
FEEDBACK
4
5
6
7
8
SNAA690000
BATTERY
F+
F+
F-
F-
red
Black/white
T+
65
66
9
T+
white
45

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Dv 45Dv 75Dv 100Dv 150Dv 300

Table des Matières