2.8

Improper use

The operating safety of the supplied product is only guaranteed
for conventional use in accordance with Section 4 of the oper-
ating instructions. The limit values must on no account fall
under or exceed those specified in the catalogue/data sheet.

3 Transport and interim storage

Immediately after receiving the product:
• Check the product for damage in transit
• In the event of damage in transit, take the necessary steps with
the forwarding agent within the respective time limits.
CAUTION! Risk of damage to property!
Incorrect transport and interim storage can cause damage to
the product.
• The pump should be protected from moisture, frost and
mechanical damage due to impact during transport and
interim storage.
• The device must not be exposed to temperatures outside the
range of –10°C to +50°C.

4 Intended use

The circulation pumps of the INOVA NH series are designed for
hot-water heating systems and other similar systems with con-
stantly changing volume flows. Approved fluids are heating
water in accordance with VDI 2035, water/glycol mixture at a
mixing ratio of max. 1:1. If glycol is added, the delivery data of
the pump must be corrected according to the higher viscosity,
depending on the mixing ratio percentage.
Intended use also includes following these instructions.
Any other use is regarded as incorrect use.