Operation
4.3

Installing the Front Duct Adapter

Overview
The front duct adapter provided with your machine is shipped loose and must be
installed before operating the machine. The thermostat probe must also be
installed on the inside of the duct adapter during this procedure.
Duct adapter
Your machine is supplied with either a one-way, two-way, or three-way front duct
varieties
adapter depending on the specific model. The procedure for installing a front duct
adapter is basically the same for each variety. A one-way adapter is pictured in the
illustrations below.
See topic Duct Blower Heater Option for additional information about two-way and
three-way duct adapters.
Procedure
Perform the procedure below to install the front duct adapter and thermostat probe.
1. The thermostat probe (a) is temporarily mounted on a disposable bracket (b)
inside the machine shell. Remove and set aside the mounting screw (c) to
disconnect the bracket from the machine shell.
2. Remove the screw fastening the thermostat probe to the disposable bracket,
and discard the bracket. Temporarily rest the thermostat probe inside the
machine shell.
Note: Do not discard the screw. It will be used to mount the thermostat probe.
3. Slide the edge of the duct adapter (d) beneath the edges of the upper and lower
machine shell.
4. Align the four threaded mounting holes (e) on the duct adapter with the
corresponding holes on the machine shell.
5. Use the screws (provided) to fasten the duct adapter to the machine shell.
6. Align the thermostat probe inside the duct adapter as shown. Fasten the
thermostat probe in place using the reserved bracket screw.
c
b
a
a
28
HI400HD D / HD G
e
d
wc_gr007766
ghi_tx001462gb_FM10.fm