1. Safety Instructions
For skilled electricians and instructed personnel in accordance
with national regulation, including the relevant standard and, whe-
re applicable, in acc.with IEC 60079-17 on electrical apparatus for
explosive atmospheres.
The luminaires must not be operated in Zones 0.
The tecnical data indicated on the luminaires are to be observed.
Changes of the design and modifi cations to
not permitted.
The luminaires shall be operated as intended and only in undama-
ged and perfect conditions.
Only genuine EATON spare parts may be
ment.
Repairs that affect the explosion protection,
out by EATON or a qualifi ed "electrician" and will subsequenctly
have to be cheked by an "expert".
Do not keep these operating instructions inside the luminaire du-
ring opertion.
The national safety rules and regulations for prevention of acci-
dents and the following safety instructions which are marked with
an in theses operting instructions, will have to be observed.
2. Conformity with standards
This equipment is conform to the standards specifi ed in the EU-Decla-
ration of conformity. It has been designed, manufactured and tested ac-
cording to the state of the art and according to EN ISO 9001 and IEC/
EN 80079-34.
The luminaire are suitables for use in explosive atmospheres,Zone 1
and 2 acc. to IEC/EN60079-10.
3. Technical data
Marking:
Certifi cates:
Serie of types:
Lamps to be use:
Lampholder:
Approval of the production
ATEX Quality assurance:
Degree of protection acc. EN60598:
Insulation class acc. EN60598:
Temperature of use:
Rated voltage Luminaires
without Electromagnetic:
Standard:
On request:
Electronic:
Material of enclosure:
Material of glass:
Storage temperature in original Packing: -40ºC a + 60ºC
Terminals capacity:
Entries of cables
Direct entry:
Dimensions:
4. Installation
The respective national regulations as well as the general rules of
engineering which apply to the installation and operation of explo-
sion protected apparatus will have to be observed.
Transport and storage of the luminaire is permitted in original pac-
kaging only.
Pay attention when mounting or repairing the luminaire, dont da-
mage the fi re-fi nish of the glass adquired during moulding (abra-
sions, sanding, etc.) that can weaking their mechanical functions.
Number maximum to lamp with electronic ballats: See table 6
Opening and closing the luminaires
The opening of luminaire always shall be without voltage.
The luminaire is well closed when the cover is completly threaded
on the luminaire enclosure.
See secuency in fi gure 4.
Notes:
3)
Installed in areas without mechanical risk, due the nomal operation
in the industrial processe.
4)
See thermal class in table 2
Warning
To avoid the risk of fi re, explosion, or electric shock, this product
should be installed, inspected, and maintained by a qualifi ed
electrician only, in accordance with all applicable electrical codes.
the luminaires are
used for replace-
may only be carried
II2G Exd IIC
4
)
LOM 02 ATEX2019X
3
)
See Table 1
See Table 1
acc.EN 60061-2
LOM 02 ATEX 9040
IP 67
I
-20ºC to +40ºC
-20ºC to +55ºC
230V +10%; 50Hz λ>0.90
220-230V;50/60Hz
198-254V;50/60Hz λ>0.95
175-280 VDC
Metal aloy aluminium without
Cu,painted polyester grey.
Borosilicate
2x2,5mm2 PE ext.: 2 x 6mm2
2 x ¾" NPT, one plugged
See fi gure 3.
Dimensions for mounting: See fi gure 3
Accesories for mounting:
See EATON Crouse-Hinds Series catalogue.

4.1 Cable entries

Mounting the selected cable entries (cableglands or seals acc.
needs) acc. type and dimensions of the main conection cable, fo-
llowing their manufacturer instructions.
The cable entries devices has to be a protection mode than Exd IIC.
Unused cabe entries have to be closed by a correspondante certi-
fi ed blanking plug Exd IIC.
If the original blanking plugs are used , these must be tightened
with 15 Nm torque.
Main conection: See wiring diagram.
4.2 Lamps mounting
Only must be mounting apropiated lamps for the supplied luminai-
re. See indications in the general label of the luminaire and in the
present instructions.
5. Taking into operation
Prior to operation check the luminaire for its proper funtioning and ins-
tallation in compliance with these operting instructions and others appli-
cable regulations.
Only carry out insulation measurements between PE and external con-
ductor L1 (L1, L2, L3) as well as between PE and N.
- measurement voltage: max. 1kV AC/DC
- min. insulation: 2 M
Then the luminaire have to be tightly closed.
6. Maintenance
Observe the national rules applicable to maintenance, servicing,
inspection and repairing of apparatus for explosive atmospheres,
as well as the general rules of engineering.
7. Servicing
The responsable of the safe use of these apparatus is the property.
When servicing, in particular those components that affect the explosion
protection , will have to cheked, e.g.:
Housing and glass for any cracks or damage.
-
The fl ameproof joint have to be clean, undameged, without corrosion
-
and perfect greassed.
Gaskets for their perfect conditions.
-
Cable entries whitout corrosion.
-
Terminlas and blanking plugs for their fi rm fi x.
-
Lamp replacement in acc. with the manufacturer instructions.
-
Type of lamps used in acc. with the luminaire specifi cations.
-
The fl ameproof of these apparatus have to be greassed perma-
nentlly in order to ensure it protection in front of the corrosion,
water ingrees and seize-up problems. Cleaning rest of greasse
and corrosion no using sharp metallic devices who can damage
the surface of the joint, and greasing they using apropiate greasse
thermically and chemically stable, like e.g.: Molikote® BR2 plus.
When the housing need to be repeinted, pay attention that the fl a-
meproof joints rest without traks of coating.
8. Inspection
The nationals regulations have to be observed.
E.g. in Spain the inspections of the installations in hazardous areas,
have to be done by "qualifi ed" personnel in accordance with the Elec-
trotechnical Low Votage Regulation following the indications stablished
in IEC/EN 60079-17.
When the inspections are in degree of "Detailled" or "Closed", the
luminaires have to be disconnected from the main conection.
9. Repairing
The nationals regulations have to be observed. The tasks of repai-
ring have to be made by "qualifi ed" personnel!
The reparation of the sealed part between the housing the glass
have to be done by
Cooper Crouse-Hinds, S.A.
The users are not authorized to repair this sealed part.
¡All reparations have to be done without voltage!
For repair electrical equipments in protection mode is suggested follow
the instructions indicated in IEC/EN 60079-19.
Only use genuine EATON Crouse-Hinds
Subject to alteration or supplement of this product without any adverti-
sement before.
Save these instructions for future reference.
All statements, technical information and recommendations contained
herein are based on information and tests we believe
to be reliable. The accuracy or completeness thereof are not gua-
ranteed. In accordance with Crouse-Hinds "Terms and Conditions of
Sale" and since conditions of use are outside our control, the purcha-
ser should determine the suitability of the product for his intended use
and assumes all risk and liability whatsoever in connection therewith.
Series spare parts.