Installation of the fitting for wall installation

7.1
Remove the cover plate.
Details can be found in the installation and operating instructions for the fitting.
7.2
Use an Allen key to close the water volume regulators.
a: closed
b: open
7.3
Trigger the fitting.
Spare part
7.4
Disconnect the power supply from the AQUACONTACT sensor.
7.5
Disconnect the cable connection between the solenoid valve cartridge and the
AQUACONTACT sensor.
7.6
Remove the screws (c).
7.7
Remove the solenoid valve cartridge (d).
7.8
Use flat-nosed pliers to remove the filter (e).
7.9
Continue with
Retrofitting thermal disinfection
7.10 Disconnect the power supply from the AQUACONTACT sensor.
7.11 Remove the screws (f).
7.12 Remove the sealing plug (g).
Pull the sealing plug out from the centre thread using an M8 size screw.
7.13 Insert the new filter.
Important!
Note the installation position. The crosspiece of the filter must not be over the flow
hole.
7.14 Insert the solenoid valve cartridge.
7.15 Tighten the screws.
7.16 Connect the cables between the solenoid valve cartridge and the AQUACONTACT
sensor (k).
l: Solenoid valve cartridge mixed water (AQUACONTACT: black cable)
m:Solenoid valve cartridge thermal disinfection bypass (AQUACONTACT: red cable)
Important!
The solenoid valve must be connected before the power supply is connected.
7.17 Connect the power supply to the AQUACONTACT sensor.
Work step
7.13.
5