Marking

TECHNICAL DATA

Certification
Product standard
Electrical:
Operating voltage U
Rated current I
Current switch-off
(in case of overload or short circuit)
Switch-off times for
electronic switch-off
Capacitive loads
Inductive loads
Service life when used as a relay
Mechanical:
Number of channels
Width
Height
Depth
Input terminals (optional)
Output terminals
Terminal type
Terminal capacity
Communication port
Terminal type
Terminal capacity
Busbar
Assembly
Status LED
Slide switch
7
Eaton Industries (Austria) GmbH, Eugenia 1, 3943 Schrems, Austria
© 2018 by Eaton Industries (Austria) GmbH, www.eaton.eu/documentation
B
N
CE
UL508 + UL2367 (section 10 and 12)
Applicable sequences of:
EN60947-1, EN60947-5-1, EN61009-1,
EN61131-2 and EN61000-4-2
Details see In-House Standard WN 1008
24V DC (16....30 V DC)
Fix; 2, 4, 6, 8, 10, 13, 16A
Typically 1.3 x I
with active current limitation to
N
1,25 x l
N
see time / current table
Up to 20,000 μF
I
≤ 6A ... τ
≤ 60ms
n
max
6A < I
≤ 10A ... τ
≤ 12ms
n
max
10A < I
≤ 16A ... τ
≤ 7,5ms
n
max
see time / current table
1
17.5 (1 HP)
92.5mm
119.2mm
3 x LINE (+) and 3 x GND (-)
3 x LOAD (+) and 3 x GND (-)
Push-in terminals
2.5mm² (flexible with ferrule)
4mm² (rigid)
2 x remote signaling output (internally linked)
2 x remote signaling input (internally linked)
1x GND
Push-in terminals
1 mm² (flexible with ferrule)
1.5mm² (rigid)
LINE (+) and GND (-); max. 80A
In different lengths up to 1m
Snap-fit onto the TH35 mounting rail (EN 60715)
Two-colored; Green = OK; Red = Tripped
Off = channel not in operation
On/Off/Reset