Wilo ElectronicControl Notice De Montage page 27

Masquer les pouces Voir aussi pour ElectronicControl:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 33
English
Display
ROTATION SENSE
0
MIN SPEED
30
HZ
DRY RUN PROT
NO
PRESSURE SETTING
2,0
BAR
START DELTA P
0,3
BAR
TIME BEFORE STOP
5
S
DISPLAY
STANDARD
RUNNING TIME
HOURS
23
Menu level 1
Hz
HISTORIC
26H
Menu level 2
Description
ROTATION
Setting of the rotation
SENSE
sense. See the pump
identification plate.
Push on
the pump (at 30hz)
and check the rotation
sense.
MIN SPEED
Define the minimum
motor rotation speed
DRY RUN PROT
If the installation is
provided with a level
switch (flow switch or
other ones) change NO
by YES.
PRESSURE
Working pressure set-
SETTING
ting in the installation
Start delta P
Define the starting
pressure as : starting
pressure = setpoint
pressure - start delta
P.
TIME BEFORE
Time setting before
STOP
pump stop when there
is no flow.
DISPLAY
Define the display
mode :
• STANDARD:network
• SERVICE : rotation
RUNNING TIME
Total pump running
hours (H).
to start
pressure (bar) +
pressure setting
(bar)
frequency (Hz) +
pressure setting
(bar) + networkpres-
sure (bar) + flow
switch detection (1
or 0)
WILO SE 05/2011

Publicité

Table des Matières
loading

Table des Matières