Set Zero Menu

!
Only use the Set Zero function when the unit no longer displays zero. See
Periodic Inspection and
This option allows users to set the sensor zero. Scroll to the Set Zero
main menu option and press enter to begin.
Before starting calibration, connect the regulator to the
appropriate cylinder (nitrogen for all sensors except the
combustible sensor, which uses air).
Adjust the flow rate to the indicated rate.
Connect the tubing from the regulator to the sensor calibration
cap.
Let the gas flow for at least 3 minutes before starting calibration.
In the main Set Zero screen, press
The next screen requests confirmation. Use the up or down
buttons to display Yes and press enter to confirm.
E
Point Network Gas Monitor User Manual
3
Using the Programming Menus
Maintenance.
* Menu *
Set Zero
Set Zero
Yes
Main Menu Options List
enter to begin.
19