Installation Dimensions
36" (91.4 cm) or 48" (121.9 cm)
or cabinet opening width
(if installed between cabinets)
18" (45.7 cm) min.
clearance upper
cabinet to countertop
36" (91.4 cm)
countertop height
IMPORTANT:
Minimum distance "X": 24" (61 cm) from electric cooking
surfaces
Minimum distance "X": 30" (76.2 cm) from gas cooking
surfaces
The chimneys can be adjusted for different ceiling heights. See
the following chart.
Vented Installations
Min. ceiling height
Electric cooking
7' 9" (2.36 m)
surface
Gas cooking
8' 3" (2.51 m)
surface
* NOTE: The range hood chimneys are adjustable and de-
signed to meet varying ceiling or soffit heights depending on
the distance "X" between the bottom of the range hood and
the cooking surface. For higher ceilings, an Extension Kit Part
Number W10352733 is available from your dealer or an au-
thorized parts distributor. The chimney extension replaces the
upper chimney shipped with the range hood.
6
See Note*
X*
Max. ceiling height
10' 2" (3.1 m)
10' 2" (3.1 m)

Venting Requirements

Vent system must terminate to the outdoors.
Do not terminate the vent system in an attic or other
enclosed area.
Do not use 4" (10.2 cm) laundry-type wall caps.
Use metal vent only. Rigid metal vent is recommended.
Plastic or metal foil vent is not recommended.
The length of vent system and number of elbows should be
kept to a minimum to provide efficient performance.
For the most efficient and quiet operation:
Use no more than three 90° elbows.
Make sure there is a minimum of 24" (61.0 cm) of straight
vent between the elbows if more than one elbow is used.
Do not install two elbows together.
Use clamps to seal all joints in the vent system.
The vent system must have a damper. If the roof or wall
cap has a damper, do not use the damper supplied with the
range hood.
Use caulking to seal exterior wall or roof opening around
the cap.
The size of the vent should be uniform.
Cold weather installations
An additional back draft damper should be installed to minimize
backward cold air flow, and a thermal break should be installed
to minimize conduction of outside temperatures as part of the
vent system. The damper should be on the cold air side of the
thermal break.
The break should be as close as possible to where the vent
system enters the heated portion of the house.
Makeup air
Local building codes may require the use of makeup air systems
when using ventilation systems greater than specified CFM of air
movement. The specified CFM varies from locale to locale.
Consult your HVAC professional for specific requirements in
your area.
Venting Methods
Typical Internal Blower Motor System Venting Installations
A 10" (25.4 cm) round vent system is needed for installation
(not included). The range hood exhaust opening is 10" (25.4 cm)
round.
NOTE: Flexible vent is not recommended. Flexible vent
creates back pressure and air turbulence that greatly reduce
performance.
Vent system can terminate either through the roof or wall.
To vent through the wall, a 90º elbow is needed.
Roof Venting
A
B
A. Roof cap
B. 10" (25.4 cm)
round vent
Wall Venting
B
A
A. Wall cap
B. 10" (25.4 cm)
round vent