Transmission On Overpass Threshold; Important - ADEUNIS Sigfox BREATH PM1 Guide Utilisateur

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Sigfox BREATH - Guide utilisateur / User guide version V1.0.0

2.3.2 Transmission on overpass threshold

The product allows the detection of a threshold for TVOC and PM :
The product sends an alarm if a threshold is overpassed or if the measure turn back to normal.
FR
EN
Value <
No
(threshold -
hysteresis)
Yes
Deactivation alarm
Standby
PM & TVOC
measure
Yes
Alarm acti-
vated
?
No
Value >
No
high thresh-
old
Yes
Alarm activation
Send 0x6E frame
Example:
Register
Encoding
Value
S301
Decimal
0
S330
Decimal
0
S340
Decimal
1
S341
Decimal
50
S342
Decimal
5
S350
Decimal
3
S351
Decimal
25
S352
Decimal
2
S360
Decimal
0
In this example:
• The product send an alarm if:
• the PM10 value measured is higher than 50 µg/m3
• and/or PM2.5 value measured is higher than 25 µg/m3
• The alarm is deactivated if:
• the PM10 value measured is lower than 45 µg/m3
• and/or PM2.5 value measured is lower than 23 µg/m3
NOTE: as indicated it is possible to combined the periodical and the
alarm mode.
IMPORTANT: the product measure the data every seconds, it is then
advised to configure an important hysteresis to avoid the transmission
of too many alarm frames.
Result
Event mode (no periodical
transmission)
No TVOC alarm
Activated alarm for PM10
50 µg/m3 threshold for PM10
5 µg/m3 hysteresis for PM10
Activated alarm and activated
LED for PM2.5
25 µg/m3 threshold for PM2.5
2 µg/m3 hysteresis for PM2.5
No PM1 alarm
Page
46
of 52

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Sigfox breath pm2.5Sigfox breath pm10Sigfox breath tvoc

Table des Matières