Beretta Exclusive Boiler Green HE 25 B.S.I. Manuel D'installation Et D'utilisation page 22

Masquer les pouces Voir aussi pour Exclusive Boiler Green HE 25 B.S.I.:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 166
EXCLUSIVE BOILER GREEN HE B.S.I.
16 - ADJUSTMENTS
The boiler has already been factory adjusted by the manufacturer.
If a new adjustment is required, for example, after extraordinary
maintenance, replacing the gas valve or converting from natural
gas to LPG, proceed as follows.
Maximum and minimum power, minimum and maximum
heating, must be adjusted in the indicated sequence by
qualified staff.
- Loosen the two fixing screws (A) and remove the shell (fig. 3)
- Lift up the panel and turn it forwards
- Loosen the pressure tap screw downline from the gas valve by
about two turns and connect the pressure gauge to it
CALIBRATION & SERVICE operations must be performed with
the boiler in the OFF position. To do this, press the
until the display shows "- -" (fig. 43).
During parameter modification operations, the "select functions"
button acts as an ENTER (confirm) button, the
an ESCAPE button. If no confirmation is given within 10 seconds,
the value is discarded and returns to the previously set one.
Setting the password
Press and hold down the operating mode button and the
together for about 10 seconds. The display will look like fig. 44.
Enter the password for accessing the parameter modifications
function by turning the domestic hot water temperature selector to
the required value.
The password is located on the back side of the control panel.
Confirm by pressing ENTER.
Calibration phases
Turn the domestic hot water selector to sequentially scroll the
CALIBRATION & SERVICE phases:
- 1
gas type
- 2
boiler power (do not modify this parameter)
- 10 domestic hot water mode (do not modify this parameter)
- 3
insulation level of building (only if external sensor is connected)
- 45 inclination of thermoregulation curve (OTC), only if external
sensor is connected)
- 47 inclination of thermoregulation curve 2CH (OTC), only if
external sensor is connected)
- HP maximum fan speed (do not modify this parameter)
- LP minimum fan speed (do not modify this parameter)
- SP ignition speed (do not modify this parameter)
- HH boiler at maximum power
- LL boiler at minimum power
- MM fan ignition speed (do not modify this parameter)
- 23 maximum heating adjustment possibility
- 24 minimum heating adjustment possibility.
The parameters 2 - 10 - HP - SP - LP - MM - 23 - 24 must be
modified, by professionally qualified personnel, only if ab-
solutely necessary. The manufacturer refuses any respon-
sibility in the case of incorrect setting of the parameters.
MAXIMUM VENTILATOR SPEED (P. HP)
- Select parameter HP
- Press the ENTER button, then modify the value of the parameter
by turning the sanitary water temperature selector. The maximum
speed of the fan is linked with the type of gas and the power of
the boiler, table 1
- Turn the sanitary water temperature selector in order to adjust the
set value
- Confirm the new value you have set by pressing ENTER.
The value indicated on the display is expressed in revs min/100
(example 3600 = 36).
The value set during this operation automatically modifies the maxi-
mum value of parameter 23.
table 1
MAXIMUM NUMBER OF
FAN REVOLUTIONS
25 B.S.I.
35 B.S.I.
22
button
button acts as
button
G20
G31
60
60
revs/min
60
59
revs/min
MINIMUM VENTILATOR SPEED (P. LP)
- Select parameter LP
- Press the ENTER button, then modify the value of the parameter
by turning the sanitary water temperature selector. The minimum
speed of the fan is linked with the type of gas and the power of
the boiler, table 2
- Turn the sanitary water temperature selector in order to adjust the
set value
- Confirm the new value you have set by pressing ENTER.
The value indicated on the display is expressed in revs min/100
(example 3600 = 36).
The value set during this operation automatically modifies the maxi-
mum value of parameter 24.
table 2
MINIMUM NUMBER OF
FAN REVOLUTIONS
25 B.S.I.
35 B.S.I.
VENTILATOR IGNITION SPEED (P. SP)
- Select parameter SP
- Press the ENTER button, then modify the value of the parameter
by turning the sanitary water temperature selector. The standard
slow start value is 3700 revs/min (25 B.S.I.), 3300 revs/min (35
B.S.I.)
- Confirm the new value you have set by pressing ENTER.
MAXIMUM POWER ADJUSTMENT (P. HH)
- Turn the boiler OFF
- Select the parameter HH and wait for the boiler to come on
- Check that the maximum CO
paragraph "Checking combustion parameters) corresponds with
the values indicated in table 3.
If the CO
proves to comply with the values in the table, proceed to
2
adjust the next parameter (LL - adjusting the minimum), if different
modify the value by turning the maximum power adjustment screw
with a screwdriver (clockwise to decrease) until you obtain a value
contained in table 3.
table 3
CO
MAX
2
25 B.S.I.
35 B.S.I.
Maximum power
adjusting screw
Minimum power
adjusting screw
47
G20
G31
12
19
revs/min
12
19
revs/min
reading on the analyser (see
2
G20
G31
9,0
10,0
%
9,0
10,0
%

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Exclusive boiler green he 35 b.s.i.Green he 25 b.s.i.Green he 35 b.s.i.

Table des Matières