Installing the unit

6. Installing the unit
Before installing the unit, the packaging must be removed, taking special care not to damage the housing.
Check that there is no condensation inside the packaging. If there are signs of condensation, the unit must not be
installed until you are sure it is completely dry.
CAUTION
All installation operations must comply with current regulations.
All operations involving moving heavy weights must be carried out by two people.
If the PV installation is in France, the stickers indicated in standards C18-510 and C15-712-1/2/3 must be
firmly placed on each inverter.

6.1. General requirements for installation

The environment of the unit must be appropriate and meet the guidelines described in chapter "5.
Preparation for installing the unit". Additionally, the parts used in the rest of the installation must be
compatible with the unit and comply with the applicable legislation.
The ventilation and workspace must be suitable for maintenance tasks according to the applicable
regulations in force.
The external connection devices, which must be suitable and sufficiently close as set forth in current
regulations.
The feed cables must be of the appropriate gage for the maximum current.
Special care must be taken to ensure that there are no external elements near the air inlets and outlets
that obstruct proper cooling of the unit.

6.2. Attaching the unit to the wall

INFO
These inverters can be installed together with a connections box. If using the connections box provided by
Ingeteam, it can be installed attached to the lower part of the inverter or separated from it.
If you want to install the connections box annexed to the lower part of the inverter, see the installations manual
for the connections box to proceed with the installation of the inverter-connections box group, and do not follow
the instructions below.
If you want to install the connections box separate from the inverter, follow the instructions below to install the
inverter, and see the connections box installation manual for installing the latter.
If you do not want to install a connections box, follow the instructions described below to install the inverter.
These units have a system for securing them to the wall using a plate. The steps for fixing the unit properly are as
follows. The weight of the unit must be taken into account.
The top attachment plate for the unit supports the weight. The bottom point fixes the inverter to the wall and
prevents vibrations.
CAUTION
It is mandatory to follow the order described above. Do not switch on the power until you have made all the
connections and closed the unit.
ABO2011IQM01_C - Installation and Operation Manual