Store the instrument in its original packaging in a location that fulfils the conditions
listed above. If the original packaging is not available, pack and store the instrument as
described below:
1. Wrap the instrument in an antistatic plastic film.
2. Place the instrument, along with shock-absorbent material, in the packaging.
3. If stored for a prolonged period of time (more than 30 days), place a bag containing a
desiccant inside the packaging.

5. Commissioning, operation

5.1 Mounting the instrument

Requirements for mounting point
The mounting point must meet the following conditions:
Sufficient space for a safe electrical installation.
Permissible ambient and medium temperatures remain within the performance limits.
Consider possible restrictions on the ambient temperature range caused by mating
connector used.
→ For performance limits see chapter 9 "Specifications"
Sealing variants
Parallel threads
Seal the sealing face  with flat gasket, lens-type
sealing ring or WIKA profile sealing.
Tapered threads
Wrap threads with sealing material
(e.g. PTFE tape).
WIKA operating instructions, OEM pressure sensor, model MH-3
per EN 837
(formerly DIN 3852-E)
NPT, R and PT
per ISO 1179-2
9
EN