3.4 GAS TRAIN,

(as EN 676)
The gas train is supplied separately, for its adjustment see the enclosed instructions.
GAS TRAIN
TYPE
MB DLE 055 D01
3970562
MB DLE 403 B01
3970085
MB DLE 405 B01
3970086
MB DLE 405 B01
3970087
MB DLE 407 B01
3970069
MB DLE 407 B01
3970088
MB DLE 410 B01
3970092
MB DLE 412 B01
3970093
3.5

GAS TRAIN ELECTRICITY SUPPLY

The gas train's power cables can be fed to the right or
left of the burner, as illustrated in figure 6.
Depending on the entry point, the cable clamp with
pressure test point (1) and simple cable clamp (2) may
need swapping over.
Consequently, you must make sure:
cable clamp (1) is positioned correctly;
the tube is positioned correctly so that there are no
restrictions likely to impede air flowing to the pres-
sure switch.
WARNING
If necessary, cut the tube to the right size.

3.6 GAS FEEDING LINE

1
– Gas supply pipe
2
– Manual cock (charged to the installer)
3
– Gas pressure gauge (charged to the installer)
4
– Filter
5
– Gas pressure switch
6
– Safety valve
7
– Pressure governor
8
– Adjusting valve
M1 – Gas-supply pressure test point
M2 – Pressure coupling test point
2146
MATCHED
BURNER
CODE
BS1
BS1
BS1
BS2
BS2
BS3 - BS4
BS3 - BS4
BS3 - BS4
1
CONNECTIONS
INLET
OUTLET
Rp 1/2
Flange 1
Rp 1/2
Flange 1
Rp 1/2
Flange 1
Rp 3/4
Flange 2
Rp 3/4
Flange 2
Rp 3/4
Flange 3
Rp 1 1/4
Flange 3
Rp 1 1/4
Flange 3
1
2
2
3
M1
4
5
D5209
6
GB
USE
Natural gas and LPG
Natural gas ≤ 40/45kW and LPG
Natural gas and LPG
Natural gas and LPG
Natural gas and LPG
Natural gas ≤ 150kW and LPG
Natural gas and LPG
Natural gas
D4605
6
7
8

Fig. 6

2
1
Fig. 7
M2