13. Troubleshooting

Error messages
The sauna control unit is equipped with diagnostic software which monitors
system statuses at start-up and during operation. As soon as the diagnostic
software identifies an error, the sauna control unit switches the sauna heater off.
Errors are indicated by a recurring warning tone emitted by the power unit and
by the flashing lights on the LED wheel
error number is displayed with the help of the power level display
of LEDs on it which are flashing indicates the error number. The following table
describes the errors which may occur, and their causes. If necessary, tell the
error number to your customer service specialist.
Switch the sauna control unit off on the power unit using the ON/OFF switch A
and rectify the error before switching the sauna control unit on again.
Error
Description
01
Safety shut-off
02
Excess temperature
fuse
03
Communication error
04
Heater sensor error
05
Foil sensor error
06
Bench sensor error
08
Foil sensor
excess temperature
on the operating unit. Furthermore, the
c
Cause / rectification
The safety shut-off function is deactivated
on this sauna control unit. A wire jumper
has been connected to the "OSG" ter-
minal in the factory. Inspect this jumper,
if necessary.
The maximum temperature of 139 °C
above the heater has been exceeded.
No power unit has been connected,
or the contact is poor.
Defective heater sensor, poor contact,
or short circuit.
Defective foil sensor, poor contact
or short circuit.
Defective bench sensor, poor contact
or short circuit.
The maximum foil temperature of 100 °C
was exceeded.