Ice cubes are
cloudy
Ice capacity of the
ice cube maker
too low
Water spills over
the edge of the
tub during ice
cube production
User-manual-HighLine-v.02
Tub motor no longer
running
1. Condenser is
soiled
2. Insufficient
ventilation
3. Room / ambient
temperature is too
high
4. Cooling water
controller not
working properly
1. Machine is not
level
2. Tube has moved
down
3. Water level
sensor is soiled
Check tub motor voltage. If
voltage is present and the tub
motor does not turn, replace
the tub motor
tub motor
1. Clean condenser
Clean condenser
2. Check specified lateral
distances and ensure optimum
air circulation
3. Reduce room/ambient
temperature, if necessary
relocate the machine. Replace
air-cooled machine with water-
cooled machine if necessary
4. Check cooling water
controller, setpoint temperature
+30°C, readjust or replace if
necessary
1. Align machine
2. Readjust tub
3. Clean / descale water level
sensor
01/2021
61