Mounting probe with temperature buffer
It is mandatory to have a galvanic connection between the blue (GND) wire and the protective wire
(potential earth)! With metal containers the function earth (BE-conncetion) is normally made through
the threading of the probe to the metal container. With non-metal containers and probes without con-
nection heads the connection to this earth is made by means of a direct cable connection to the blue wire
of the cable. The probe also can be mounted upside-down.
D
≥15 mm
Non-active range 1 (IB1)
Measuring area (M)
Non-active range shield (IBS)
Area temperature buffer (TP)
Non-active range holder (IBH) Do not mount the measuring range in the area of the
container with changes in the cross section, like the bottom cone of the container
The probe can be mounted in the centre of the container or just off to one side. For a measurement to be independent of the
filling cone, we recommend that the probe be mounted at ¼ of the diameter. The minimum distance between the end of the
measuring range and the container's lid is 50 mm.
Technical Data
Electrical version
Output function for KFW-51...TP...ETW
Output function for KFW-52...TP...ETW
Operating voltage (U
B
Permitted residual ripple max.
Output current max. (I
Power consumption max. (outputs no-load)
Permitted ambient temperature
Permitted ambient temperature (for active zone)
LED-Display
Protective circuit
Degree of protection IEC 60529
Norm
Connection cable
*Where applicable
** For further technical data: See data sheet
¼D
IBH
TP
IBS
M
IB1
)
)
e
1/3D,
min. 50 mm
5-wire DC
1 limit value switching point, normally open
2 limit value switching points, normally open
15...30 V DC
5 %
100 mA
0,9 W
-25...+70 °C
-25 up to +200 °C**
Green
Built-in
IP 67
EN 60947-5-2*
2 m, PVC, 5 x 0,34 mm²
KFW-51(2)-ETW
BE
Connect the BE (function earth)
direct to the blue wire of the
cable.
25